free shipping on orders over $100*

Deringer 40 (RP)

Reduced Pressure Backflow Preventer

SKU
Deringer 40
MSRP: $11,659.00 MSRP: $11,659.00 Pro Price: $2,229.00 Pro Price: $2,229.00 Special Price $0.00
Price includes standard ground shipping.

Deringer 40 Reduced Pressure Valves prevent non-health hazard pollutants and hazardous contaminants from entering a potable water supply system when backpressure and/or backsiphonage conditions occur. Used primarily on fire sprinkler systems.

Deringer Approvals

Deringer 40 Reduced Pressure Backflow Preventer stops non-health hazard pollutants and hazardous contaminants from entering a potable water supply system when backpressure and/or backsiphonage conditions occur. The Deringer 40 is used primarily on fire sprinkler systems when monitoring of unauthorized water use is required.

 

Deringer 40

Maximum Working Pressure: 175psi (12.1 bar)
Temperature Range: 33 to 140 deg F (1 to 60 deg C)
Lead Free: 0.25% Maximum by Weight

End Connections:
Flange Adapters: ANSI B16.1 Class 125
IPS Groove for Steel Pipe: AWWA C606

Rate of Flow:

Rate of Flow Deringer 40

Dimensions:

Deringer 40 measurements

Materials:

Valve Housing: 304 Stainless Steel
Valve Cover: 304 Stainless Steel
SOV Disks: EPDM/304SS
SOV Shafts: 304 Stainless Steel
RV Spring: 302 Stainless Steel
SOV Bearings: Teflon/Bronze
Non Wetted Bolts: Grade 8 Zinc Plated
Check Disks: Silicone
Wetted Fasteners: 18-8 Stainless Steel
RV Housing: 304 Stainless Steel
Check Springs: 17-7 Stainless Steel
Check Pins: 17-7/18-8 Stainless Steel
Check Seats: Noryl Polymer
O-Rings: Buna-N
RV Hose: Braided Stainless Steel Wire

Engineering Specifications

The Deringer 40 Reduce Pressure (RP) valve shall utilize two independent check modules and two integral resiliently seated shut-off valves all of which shall be contained within a single rigid valve housing constructed entirely of 304 stainless steel. Both integral shutoff valves shall include pre-wired supervisory tamper switches contained within a weatherproof actuator housing approved for both indoor and outdoor use. Dual Action Check modules shall operate as a poppet style check under low flow conditions, operate as a swing style check under high flow conditions and utilize replaceable silicone elastomer sealing discs. Assembly test cocks shall be handle-less and operate via a tamper resistant actuator. Assembly shall have a single full access service port and cover with an inline replaceable elastomer seal. Relief Valve shall operate using only static seals (zero dynamic/sliding seals). All wetted surface Relief Valve components shall be constructed of stainless steel. Assembly shall be serviceable without special tools and approved for horizontal applications.

Maximum Relief Valve Discharge Rates

Deringer 40 Max Discharge

Deringer Specification Sheets

The Deringer 40 Specification Sheet includes information on valve characteristics, flow performance data, approval status and engineering specifications for all sizes. This file can be downloaded as a PDF and saved for future use.

Deringer 40 Specification Sheet

Maintenance Instructions

The Deringer 40/50 Maintenance Instructions provide step by step procedures for maintaining a 2 to 4 inch Deringer 40/50 backflow preventer. A printable PDF document and video of these instructions are both available.

Deringer 40/50 Maintenance Instructions

Maintenance Video - 2 to 4" Deringer 40

Tamper Switch Procedure

The Deringer Gear Box Tamper Switch Procedure provides a step by step instructions for positioning the wiring of the Deringer gear box for fire alarm protection. A printable PDF document of these instructions is available.

Tamper Switch Instruction

Gear Box Wiring Instructions

The Deringer Gear Box Wiring Installation Instructions provide step by step procedures for wiring the Deringer gear box for fire alarm protection. A printable PDF document of these instructions is available.

Gear Box Wiring

Gear Box Replacement

Indicator Flag Adjustment

The Indicator Flag Adjustment Instructions provides a step by step procedure for aligning the flag to fully open and fully close on the backflow preventor gear box. A printable PDF document of these instructions is available.

Indicator Flag Position

True-Seal Check Modules

The True Seal Check Valve was designed to incorporate a poppet only motion during the check stroke and is used exclusively on the first check assembly on the Deringer RP and RPDA models and Magnum RP model. This design allows a more consistent pressure loss across the check valve which helps maintain a steady and continual closure of the Relief Valve.

  • Light weight engineered polymer components
  • Modular for easy removal of complete check from body
  • Easily disconnect spring tension for safe check servicing
  • Replaceable Silicone Rubber Elastomer Disk
  • Excellent resistance to fouling.
True-Seal Check Modules

Poppet Action

Deringer and Magnum 40/50 Low Flow Poppet Action

Features:

  • 100% of check stroke is that of a poppet check
  • Consistent static sealing
  • Excellent resistant to fouling
  • Reliable check closure
  • Stable flow characteristics at ALL flow rates

Dual-Action™ Check Modules

The Patented Dual-Action Check™ (US8875733) is the core technology behind the superior performance of Deringer Backflow Prevention Product Line. The Dual-Action Check™ combines all of the best features of industry standard “poppet” checks and “swing” checks into a single high performance check module.

  • Light weight engineered polymer components.
  • Modular for easy removal of complete check from body.
  • Easily disconnect spring tension for safe check servicing.
  • Replaceable Silicone Rubber Elastomer Disk.
  • Excellent resistance to fouling
Dual Action Check Module

Poppet Action

Low Flow Poppet Action

Features:

  • Initial 25% of check stroke is that of a poppet check
  • Consistent static sealing
  • Excellent resistant to fouling
  • Reliable check closure
  • Stable flow characteristics at lower flow rates

Swing Action

Features:

  • Final 75% of check stroke is that of a swing check
  • Minimal friction loss at high flow rates
  • More linear flow path water through valve.
High Swing Action

Bow-Seal™ Full Access Cover

The Patented Bow-Seal™ Full Access Cover (US8844562) is pre-formed to cylindrical shape friendly to high fluid pressure. This allows the cover to be much thinner and lighter than traditional flat covers while still providing FULL and EASY access to Dual Action™ Check Modules.

Additional features include:

  • Light weight Simple removal
  • No sliding seals
  • Full access to valve internals
  • No cumbersome and heavy couplings
Bow Seal Access Cover

Tamper Resistant Test Cock

The Deringer tamper resistant 1/2" and 3/4" ball valves are the first handle-less test cocks found on large diameter backflow devices in the industry. The top of the valve actuation stem has a unique shape that uses an independent custom wrench to open and close test cocks. All test cocks are lead free and meet the SDWA requirements.

Deringer Tamper Resistant Test Cock

Relief Valve

The Deringer 40/50 Relief Valve uses a stainless steel body, piston seal and stainless steel sensing line and has been designed to be the smallest and lightest Relief Valve in the industry. Unlike previous relief valve designs, the piston seal does not use the body of the relief valve to align itself properly when closing and opening and instead uses the guide pin on the piston. This will aid in making the Relief Valve resistant to build up and binding. All components of the relief valve are lead free and meet the SDWA requirements.

Relief Valve Image

One Year Warranty

Backflow Direct warrants its product to be free from defects in material and workmanship under normal operating conditions for a period of one year from the date of original shipment. In the event of such defects within the warranty period, Backflow Direct retains the exclusive right to repair or replace (with a new or newly rebuilt product) the device or offer a full refund of the original purchase price at its sole discretion. Backflow Direct assumes no liability for replacement of inoperative products beyond the warranty period.

THE WARRANTIES AND REMEDIES CONTAINED HEREIN ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES EXPRESS, IMPLIED, OR STATUTORY, INCLUDING ANY LIABILITY ARISING UNDER ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, STATUTORY OR OTHERWISE.

THE REMEDY ABOVE SHALL BE THE SOLE AND EXCLUSIVE REMEDY FOR ANY BREACH OF WARRANTY. Backflow Direct shall not be responsible for any special, consequential or incidental damages, including without limitation, repair costs or lost profits or property damage as a result of product malfunction or any other costs resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, adverse water conditions or any other circumstances over which Backflow Direct has no control. SOME STATES DO NOT ALLOW THE EXCLUSION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, IN SUCH STATES, THE ABOVE LIMITATIONS MAY NOT APPLY.

This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the products.

To obtain warranty service, contact us for further instructions. When credit is issued it will be at the original purchase price.

 

Product Specific Warranty

1) NRS, OS&Y and/or any Gate Valves utilized as shut off valves on Backflow Direct products are covered by original manufacturer's warranty ONLY.

2) Reduced Pressure Principle Backflow Preventers (RP or RPDA) can and WILL discharge water. NEVER install an RP or RPDA in a location where any amount of discharge from the Relief Valve will cause property damage. For an indoor, pit, vault, mechanical room or enclosure installation of an RP or RPDA an auxiliary drain (SEPARATE AND INDEPENDENT of the Air Gap Assembly) is REQUIRED and MUST be properly sized for the Maximum Relief Valve Discharge Rate corresponding to the system/supply pressure. Backflow Direct shall not be responsible for any special, consequential or incidental damages, including without limitation, repair costs, lost profits, property damage, or any other costs resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, adverse water conditions or any other circumstances, caused by lack of auxiliary drain, location of auxiliary drain or undersized auxiliary drain.

3) Air Gap Assembly will capture and evacuate light water discharge from the Relieve Valve caused by daily fluctuation in system/supply pressure. An Air Gap Assembly will NOT capture and evacuate the Maximum Relief Valve Discharge Rate caused by catastrophic valve or system failure. An auxiliary drain (separate and independent of the Air Gap Assembly) is REQUIRED and MUST be properly sized for the Maximum Relief Valve Discharge Rate. Backflow Direct shall not be responsible for any special, consequential or incidental damages, including without limitation, repair costs, lost profits, property damage, or any other costs resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, adverse water conditions or any other circumstances, caused by lack of auxiliary drain, location of auxiliary drain or undersized auxiliary drain.

This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the products.

To obtain warranty service, contact us for further instructions. When credit is issued it will be at the original purchase price.

 

Download Warranty Information